Symptoms you may see while bringing up an NTC thermistor, their causes and the fix for each.

Start with the voltage: GetVoltage() and GetResistance() on a failing reading tell wiring and ADC problems (the voltage is wrong) apart from configuration problems (the resistance is right, the degrees are not).

Initialize() returns false

Cause Check Fix
ADC not up Your port's EnsureInitialized() Fix the SDK call
Channel missing IsChannelAvailable(adc_channel) in your port Use a channel the port accepts
Invalid config R25, supply or series resistor not positive; B outside 1000 K to 5000 K; min_temperature ≥ max_temperature; sample_count 0 Correct the value; SetConfiguration() returns InvalidParameter for the same cases
No port nullptr passed to the constructor Pass the port's address

Temperature conversion failed

The node reads 0 V or the supply, or the resistance is outside 0.1 Ω to 1 MΩ.

Cause Check Fix
Thermistor shorted or missing to the node GetVoltage() near 0 V Wiring, solder joints
Thermistor open GetVoltage() near the supply Wiring, connector, cable
Port returns counts, not volts GetVoltage() returns thousands Return volts from ReadChannelV() (Porting)
reference_voltage below the real supply GetVoltage() above reference_voltage Set the divider's real supply

Temperature out of range

The conversion worked but the result is outside min_temperature to max_temperature (−40 °C to +125 °C by default). Read GetResistance(): if it matches the thermistor's table at the real temperature, widen the window; if not, see the next section. A part near a hot spot may be right.

Off by a few degrees

Cause Check Fix
Wrong supply value Measure the divider supply Set reference_voltage to it: 1 % is about 0.5 °C at 25 °C
Wrong series resistor Measure it Set series_resistance
Uncalibrated ADC GetVoltage() against a meter Use your SDK's ADC calibration in ReadChannelV()
Beta error far from 25 °C to 85 °C The error grows with distance: +4.4 °C at −40 °C for this part LookupTable for the TDK types, Steinhart-Hart or a calibration offset (Conversion methods)
Wrong B for the part B25/50 and B25/85 differ by 1 % to 2 % Use the B for your range
Self-heating Reading drops when you lower the divider current Larger resistors, or power the divider only while sampling (Hardware)

Reading moves the wrong way

The temperature falls as the part heats: the thermistor is on the high side of the divider. Swap the two parts, or return VREF − VNODE from the port (Hardware).

Noisy readings

Cause Fix
ADC noise SetSamplingParameters(16, 0)
Slow drift or ripple SetFiltering(true, 0.1F); a smaller α smooths more
Long wire to the sensor, high source resistance C_FILT, 10 nF to 100 nF from the node to ground
Supply ripple Feed the divider from a clean rail (Hardware)

Calibration made it worse

Calibrate() corrects the reading at one temperature only: the offset is a constant, so the Beta equation's error elsewhere remains (Conversion methods). Calibrate at the temperature you care about most, with the sensor settled at the reference, and use LookupTable or Steinhart-Hart for a wide range.