The settings a TMC9660 needs before it drives a motor, in the order to apply them, with the struct for each.

Most subsystems have a configureAuto(Config) call: required fields first, optional fields with defaults, values written in a safe order and verified. Use it for bring-up; the individual setters stay available for tuning. Every snippet here is compiled from tests/docs/configuration.cpp.

Order

Step Call Why this position
1 bootloaderInit(&cfg) Clock, interfaces and feedback pins are bootloader settings (Bootloader)
2 gateDriver.configurePowerStageProtection(PowerStageProfile) Timing and protection of the power stage, before any PWM
3 currentSensing.configureAuto(...), calibrateOffsets() Offsets are measured with the motor off
4 motorConfig.configureAuto(MotorProfile) Motor type, pole pairs, PWM, current limits
5 feedbackSense.configureAuto(HallConfig / AbnConfig / SpiEncoderConfig) The sensor the loops will use
6 torqueFluxControl, velocityControl, positionControl .configureAuto(...) Loop gains and scaling
7 protection Voltage, temperature and current thresholds
8 motorConfig.setCommutationMode(...) Last: the chip starts driving as soon as it is set

Current sensing

Driver::CurrentSensing::AutoConfig cs{};
cs.shuntResistance_mOhm = 3.0f;     // from the schematic
cs.expectedPeakCurrent_A = 6.0f;    // picks the amplifier gain
if (!driver.currentSensing.configureAuto(cs) ||
    !driver.currentSensing.calibrateOffsets(true, 2000)) {  // motor off, wait up to 2 s
  return false;
}
Field Required Meaning
shuntResistance_mOhm yes Nominal shunt value
expectedPeakCurrent_A yes Highest phase current you expect; sets the amplifier gain
usePeakScaling Scale for peak rather than RMS current
actualShuntR_adc0_mOhm ... adc3 Measured shunt values per channel, if they differ from nominal

Motor

The API guide shows MotorProfile in context.

Field Required Default Meaning
motorType yes BLDC_MOTOR, STEPPER_MOTOR or DC_MOTOR
polePairs yes BLDC: rotor pole pairs. Stepper: full steps per revolution / 4
pwmFrequency_Hz yes 20 to 25 kHz is typical
maxPhaseCurrent_A yes Sets MAX_TORQUE and MAX_FLUX
direction FORWARD Swap to reverse without rewiring
pwmSwitchingScheme SVPWM Space-vector PWM for BLDC
maxFluxCurrent_A 20 % of the phase current Flux limit
outputVoltageLimit 8000 FOC output voltage limit (internal units)
idlePwmBehavior PWM off when idle
commutationMode unchanged Applied last, if set

Control loops

Driver::TorqueFluxControl::TorqueFluxConfig tf{};
tf.torqueP = 50;                    // unset gains keep the driver's defaults (50 / 100)
tf.torqueI = 100;
if (!driver.torqueFluxControl.configureAuto(tf)) {
  return false;
}

Driver::VelocityControl::VelocityConfig vel{};
vel.sensorSelection = tmcl::VelocitySensorSelection::DIGITAL_HALL;
vel.velocityP = 800;
vel.velocityI = 1;
if (!driver.velocityControl.configureAuto(vel)) {
  return false;
}

Gains are the chip's integer PI parameters. Start with the defaults, raise P until the response is fast without overshoot, then raise I to remove the steady-state error. Tune torque first, then velocity, then position.

Struct Required Notable optional fields
TorqueFluxConfig torqueP, torqueI, separateTorqueFluxLoops, enableFieldWeakening
VelocityConfig sensorSelection velocityP, velocityI, pNormalization, iNormalization, scaling
PositionConfig sensorSelection positionP, positionI, normalisation

Protection

driver.protection.configureVoltage(/*over*/ 300, /*under*/ 100);  // 0.1 V units: 30.0 V, 10.0 V
driver.protection.configureTemperature(100.0f, 120.0f);          // warning, shutdown in degrees C
driver.protection.setOvercurrentEnabled(true);

The voltage thresholds are in 0.1 V. Set them around your supply's real range: a 24 V system might warn at 30 V and 18 V. protection.configureAuto(ProtectionConfig) sets all of them at once.

Where the defaults come from

Each field's default is in its struct in inc/tmc9660.hpp and in the API reference; the chip's own reset values are in the parameter-mode reference.