ValveManager

The reason the board exists. One API for fourteen valve channels on two different driver chips: eight on/off solenoid channels on the MAX22200 and six proportional channels on the TLE92466ED. Source: ValveManager.h.

Channels

ValveChannel Chip Hardware channel Control
SOL_CH0 ... SOL_CH7 MAX22200 0-7 On / off with a hit phase and a hold phase, set by current (CDR) or by duty (VDR)
PROP_CH0 ... PROP_CH5 TLE92466ED 0-5 Regulated coil current in mA, with PWM frequency and dither

The table is kValveChannelMap in the header; FindChannel("SOL_CH3") turns a name into a channel.

API

Call Channels Notes
EnableChannel(ch), DisableChannel(ch) all Switch one output
EnableChannelsMask(uint16_t mask) all Bits 0-7 solenoids, bits 8-13 proportional
DisableAllChannels() all
IsChannelEnabled(ch) all From the manager's channel state
ConfigureSolenoidCdr(ch, hit_ma, hold_ma, hit_time_ms) solenoid Current drive: hit current, hold current, hit time
ConfigureSolenoidVdr(ch, hit_duty_pct, hold_duty_pct, hit_time_ms) solenoid Voltage (duty) drive
SetProportionalCurrent(ch, current_ma) proportional Set-point of the current regulator
ConfigureProportionalPwm(ch, frequency_hz) proportional Must be > 0
ConfigureProportionalDither(ch, amplitude_ma, frequency_hz) proportional Small oscillation that reduces valve stiction
HasFault(), HasSolenoidFault(), HasProportionalFault(), ClearAllFaults()
GetSolenoidFaults(max22200::FaultStatus&), GetProportionalFaults(tle92466ed::FaultReport&) Chip-level fault detail
GetChannelState(ch) all ValveChannelState: enabled, configured, current, duty, PWM, dither, counters
GetMax22200Handler(), GetTle92466Handler() The handlers, for chip features not wrapped here (nullptr if that chip failed)

All of them return hf_valve_err_t (or bool); calling a solenoid-only call on a proportional channel returns VALVE_ERR_CHANNEL_TYPE_MISMATCH.

Example: one solenoid and one proportional valve

#include "api/Flux.h"
#include "esp_log.h"
#include "managers/ValveManager.h"

auto& flux = Flux::GetInstance();
if (flux.EnsureInitialized() && flux.valves.IsInitialized()) {
    auto& valves = flux.valves;

    // Solenoid: 800 mA for 50 ms to pull in, then hold at 200 mA.
    hf_valve_err_t err = valves.ConfigureSolenoidCdr(ValveChannel::SOL_CH0, 800, 200, 50.0f);
    if (HfValveErrOk(err)) {
        err = valves.EnableChannel(ValveChannel::SOL_CH0);
    }

    // Proportional: 200 Hz PWM, 400 mA set-point.
    (void)valves.ConfigureProportionalPwm(ValveChannel::PROP_CH0, 200.0f);
    if (HfValveErrOk(valves.EnableChannel(ValveChannel::PROP_CH0))) {
        (void)valves.SetProportionalCurrent(ValveChannel::PROP_CH0, 400);
    }

    if (!HfValveErrOk(err)) {
        ESP_LOGE("app", "valve: %s", HfValveErrToString(err));
    }
}

The valve_manager_example and valve_cycling_test apps go further.

What start-up does

EnsureInitialized() brings up comms and GPIO, then tries each chip on its own, so the log names every missing chip:

  1. TLE92466ED: creates the handler, enters mission mode, drives its enable pin, clears the feedback freeze so the per-channel feedback registers update, and sets the supply under- / over-voltage trips to 19 V / 29 V for the 24 V valve rail.
  2. MAX22200: creates the handler with a 15 kΩ reference resistor (full-scale current 1000 mA), then reads STATUS back as a presence check: all ones, ACTIVE=0 or a channel left on means nothing answered on the chip select (the MISO line is pulled up, and the driver alone accepts all ones as a live part).

It succeeds only if both chips work (fail-closed, ADR 0005). Otherwise IsInitialized() stays false, every channel call returns VALVE_ERR_NOT_INITIALIZED, and GetManagerError() says HardwareFault (a chip did not answer) or BindFailed (its SPI device or control pins are missing). IsBankReady(ValveDriverType::MAX22200 / TLE92466) says which chip came up; that chip's handler accessor stays non-null for diagnosis. Both handlers are members of the manager, constructed in place: no heap.

Hardware enable path (SafeHold)

Both banks have an enable input that gates every output of the chip in hardware: MAX22200 ENABLE and TLE92466ED EN. ADR 0006 records the decision.

Call What it does
DropEnablePins() Drives both enables low through their GPIOs: no SPI, no mutex, no logging, works even if the manager failed to start. Latches until re-armed: EnableChannel() and EnableChannelsMask() then return VALVE_ERR_WRONG_MODE; disabling still works
RearmEnablePins() Re-runs the valve bring-up (Deinitialize() then EnsureInitialized()), which raises both enables again. Uses SPI and the mutex
IsOutputInhibited(), GetEnablePinStates(max, tle) Whether a drop is in force; whether each enable is driven high
flux::hal::ValveBank::EnablePins(bool) The facade the product's safety thread calls (flux_hal_valve.hpp); returns HalResult

The pins start low: GpioManager creates both enables driven low, and the FAULT_N lines of both chips as inputs, before any valve code runs. The drivers' bring-up raises the enables. Deinitialize() (and Flux::Shutdown()) ends with every channel off and both enables low. Nothing else in the HAL drops them: when to hold, and whether to vent a side first, is the product's decision.

// Safety thread, on a Stop-class latch: hardware first, then the SPI-level stop as today.
(void)flux::hal::ValveBank::EnablePins(false);
(void)Flux::GetInstance().valves.DisableAllChannels();

Diagnostics

GetSystemDiagnostics(ValveSystemDiagnostics&): which chips are up, configured and active channels, total activations and errors. GetChannelState(ch) gives per-channel counters. DumpStatistics() logs both.

Pitfalls

  • Configure, then enable. A solenoid enabled before ConfigureSolenoidCdr/Vdr runs with whatever its channel registers hold.
  • Currents are limited by the chip setup. The MAX22200 full scale is 1000 mA with this board's reference resistor; a set-point above it cannot be reached.
  • A dropped enable pin stays dropped. Re-arm with RearmEnablePins() (or ValveBank::EnablePins(true)); an EnsureInitialized() on a running manager does not re-arm.
  • One chip missing means no valve manager. A bench with only one driver fitted gets the other bank only through its handler, for diagnosis.
  • GetLastError() holds the last failed call; it is not cleared by a later success.
  • Valve supply off looks like a working chip on SPI with no coil current. Check the 24 V rail and GetProportionalFaults() (the TLE92466ED reports supply under-voltage).